图片名称
图片名称

XLNS water-cooled screw chiller

Summary

Water-cooled chiller small size, large refrigeration capacity, the use of imported compressor, low temperature performance is good, reliable and durable, products according to the characteristics of industrial applications design, built-in low-temperature circulating water pump and stainless steel refrigerated water tank, easy to use, all materials in contact with water are made of anti-corrosion materials, can prevent rust, corrosion, microcomputer LED quantity controller, with temperature display, set temperature, automatically adjust the frozen water temperature and compressor delay protection function, the selection of good contactors, relays and other electrical components, equipped with perfect indicators, Switch, operation at a glance, built-in electronic water level indication and alarm device, low water level automatic alarm, the operator through the control panel can grasp the water level of the refrigerated water tank, timely water replenishment, modular design, each compressor system independent, even if a system problems, will not affect the normal work of other systems. 1. The compressor of the unit adopts the original imported brand of French Maneurop, Copeland (Copeland (Copelen)/Carrier (Carrier), Germany BITZER (BITZER) and other low-temperature compressors; 2. Use refrigerants such as R404A, R410a, R22/R407C, etc., to meet the refrigeration temperature and environmental protection requirements; 3. Temperature selection range: can provide process frozen water between -5 °C ~ -60 °C (users according to different production needs, select different outlet water temperature unit specifications; 4. According to the needs of users, a variety of refrigerants (frozen water) can be selected: ethylene glycol aqueous solution, alcohol, ternary mixed solution and other alcoholic refrigerants, and the evaporator can also be designed according to anti-corrosion requirements and use calcium chloride aqueous solution.

Keywords:Closed cooling tower / Sealed cooling tower / Enclosed cooling tower

Message

Product details


Product performance

Water-cooled chiller small size, large refrigeration capacity, the use of imported compressor, low temperature performance is good, reliable and durable, products according to the characteristics of industrial applications design, built-in low-temperature circulating water pump and stainless steel refrigerated water tank, easy to use, all materials in contact with water are made of anti-corrosion materials, can prevent rust, corrosion, microcomputer LED quantity controller, with temperature display, set temperature, automatically adjust the frozen water temperature and compressor delay protection function, the selection of good contactors, relays and other electrical components, equipped with perfect indicators, Switch, operation at a glance, built-in electronic water level indication and alarm device, low water level automatic alarm, the operator through the control panel can grasp the water level of the refrigerated water tank, timely water replenishment, modular design, each compressor system independent, even if a system problems, will not affect the normal work of other systems.
1. The compressor of the unit adopts the original imported brand of French Maneurop, Copeland (Copeland (Copelen)/Carrier (Carrier), Germany BITZER (BITZER) and other low-temperature compressors;
2. Use refrigerants such as R404A, R410a, R22/R407C, etc., to meet the refrigeration temperature and environmental protection requirements;
3. Temperature selection range: can provide process frozen water between -5 °C ~ -60 °C (users according to different production needs, select different outlet water temperature unit specifications;
4. According to the needs of users, a variety of refrigerants (frozen water) can be selected: ethylene glycol aqueous solution, alcohol, ternary mixed solution and other alcoholic refrigerants, and the evaporator can also be designed according to anti-corrosion requirements and use calcium chloride aqueous solution.

 

XLS water-cooled screw chiller basic parameters

Models .XLS
100.1 135.1 180.1 195.1 235.1 260.1 305.1 320.1 350.1 385.1
Nominal cooling capacity KW 100 135 180 195 235 260 305 320 350 385
10Kcal/h 8.6 11.6 15.5 16.8 20.3 22.4 26.3 27.6 30.2 33.2
Run control mode of Run PL C programmable controller fully automatic control
Power Supply 380V/3N~/50Hz
compressor version 5-6 asymmetrical semi-hermetic twin screw compressor
quantity 1 unit
The startup type Y-Δ starts
Energy regulation 0-33-66-100% 0-25%-50%-75%-100%
Input power KW 22.6 29.8 37.3 41 49.9 54.3 61.1 64.3 70.8 78
Rated current A 39.3 51.9 64.9 71.3 86.8 94.5 106.3 111.9 123.2 135.7
evaporator version High efficiency shell-tube dry heat exchanger
Water m3/h 17.2 23.2 31 33.6 40.6 44.8 52.6 55.2 60.4 66.4
Piping pipe diameter   DN65 DN80 DN100 DN125
Water pressure drop Kpa 48 48 50 50 50 52 54 55 55 58
condenser version High-efficiency shell-and-tube heat exchanger
Water m3/h 21.5 29 38.7 41.9 50.5 55.9 65.6 68.8 75.3 82.8
Piping pipe diameter   DN65 DN80 DN100 DN125
Water pressure drop Kpa 46 46 47 47 48 49 51 53 53 56
Refrigerant type R22
Charge amount kg 20 25 30 40 45 49 52.2 60 65 75
Dimensions long mm 2283 2495 2517 2825 2822 2778 2767 2750 3147 3070
wide mm 700 900 900 900 900 900 900 900 900 900
high mm 1489 1450 1557 1570 1700 1700 1850 1852 1880 1890
The unit is slightly heavier kg 850 1050 1270 1340 1640 1680 1720 1750 2080 2300
Run slightly heavier kg 900 1150 1420 1540 1890 1940 1990 2050 2330 2550

Note: The parameter changes caused by the modification of the equipment are subject to no prior notice, and the specific parameters are mainly based on our program.

- The parameters in the nominal working condition are as follows: chilled water inlet/outlet water temperature 12°C/ 7°C; Cooling water inlet/outlet water temperature 30°C/ 35°C;
- Temperature conditions: chilled water outlet temperature range 5°C~ 15°C, cooling water inlet temperature range 19°C~ 33°C;
- The water side of the evaporator and condenser is designed to withstand a pressure of 1.0MPa;
- The dirt coefficient of the water side of the evaporator is 0.018m2°C/kW in the nominal working case and 0.044m2°C/kW on the water side of the condenser;
- In addition to the above specifications and requirements, the company can provide non-standard products according to customer requirements.

 

Related Products

Online Message

SUBMIT

Address

No. 16, Baishijian Road, Langxi Industrial Park, Anhui Province


©2022 Anhui XILENG Environmental Protection Technology Co., Ltd  Powered by www.300.cn​  Seo

Contact:

I look forward to your call anytime

Tel:+86-0510-88995799

Whatsapp:0086-18118877677

Wechat:

在线留言

提交留言